Control; Table 10-16 Set-Up Group - Control - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

10.7.8

Control

Table 10-16 lists all the register addresses and ranges or selections for the function
prompts in Set-up Group Control.
Parameter
Description
Tuning
00AC
Parameter
Selection
Automatic
0038
Switchover
Value (used with
172 selection 2
or 3)
Local Setpoint
00AD
Source (Number
of LSPs)
Power Up Mode
0082
Recall
RSP Source
0083
Setpoint
008A
Tracking
Control Setpoint
0007
High Limit
Control Setpoint
0008
Low Limit
Control Output
0087
Direction
4/07
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-16 Set-up Group – Control
Register
Data
Address
Type
Hex
Decimal
172
INT
056
FP
173
INT
130
INT
131
INT
138
INT
007
FP
008
FP
135
INT
UDC2500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = One set only
1 = 2 sets keyboard selected
2 = 2 sets with PV automatic
switchover
3 = 2 sets with setpoint (SP)
automatic switchover
R/W
Within the PV Range in
engineering units
R/W
0 = One Local Setpoint
1 = Two Local Setpoints
R/W
Control
Mode
0 = MAN
1 = AUTO
2 = AUTO
3 = LAST
4 = LAST
R/W
0 = None
1 = Input 2
R/W
0 = None
1 = LSP = PV (when in
Manual)
2 = LSP = RSP (when
switched)
R/W
0 to 100% of PV
(engineering units)
R/W
0 to 100% of PV
(engineering units)
R/W
0 = Direct
1 = Reverse
Setpoint
Mode
LSP
LSP
Last RSP
Last SP
Last Local SP
209