Honeywell UDC2500 Product Manual page 152

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Input Calibration
Sensor Type
S
T
T (low)
W5W26
W5W26 (low)
RP20-RP40
Thermocouple
Differential *
Honeywell
Radiamatic
Type RH
Type RI **
RTD
Alpha = 0.00385 per
IEC-60751 (1995)
100 ohms
100 ohms (low)
200 ohms
500 ohms
Linear
Milliamps
Millivolts
Volts
* The Factory Calibrated millivolt values for the Thermocouple Differential Input are for a pair
of J thermocouples at an ambient temperature mean of 450°F / 232°C. Other thermocouple
types and ambient temperature means may be accomplished via Field Calibration of the input,
with the range value limits being –4 mV to +16 mV for the zero and span values.
** The range values for Radiamatic Type RI are customer configurable within the limits shown.
138
PV Input Range
°F
0 to 3100
–18 to 1704
-300 to 700
–184 to 371
-200 to 500
–129 to 260
0 to 4200
–18 to 2315
0 to 2240
–18 to 1227
32 to 3216
–50 to 150
0 to 3400
–18 to 1871
0 to 3400
–18 to 1871
–300 to 1200
–184 to 649
–300 to 300
–184 to 149
–300 to 1200
–184 to 649
–300 to 1200
–184 to 649
4 to 20 mA
0 to 20 mA
0 to 10 mV
0 to 50 mV
0 to 100 mV
1 to 5 Volts
0 to 5 Volts
0 to 10 Volts
UDC2500 Universal Digital Controller Product Manual
°C
–0.092 mV
–5.341 mV
–4.149 mV
–0.234 mV
–0.234 mV
0 to 1880
0.000 mV
–46 to 66
–1.54 mV
0.00 mV
0.00 mV
25.202 ohms
25.202 ohms
50.404 ohms
126.012 ohms
4.00 mA
0.00 mA
0.00 mV
0.00 mV
0.00 mV
1.00 Volts
0.00 Volts
0.00 Volts
Range Values
0 %
100 %
17.998 mV
19.097 mV
12.574 mV
37.075 mV
22.283 mV
4.933 mV
4.62 mV
57.12 mV
60.08 mV
329.289 ohms
156.910 ohms
658.578 ohms
1646.445 ohms
20.00 mA
20.00 mA
10.00 mV
50.00 mV
100.00 mV
5.00 Volts
5.00 Volts
10.00 Volts
4/07