Honeywell UDC2500 Product Manual page 54

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration
Function Prompt
Lower Display
English
Numeri
c Code
FINLSP
203
SPRATE
204
SP Rate
operates only
when neither
SP Ramp or
SP
Programming
is running or
when SP
Ramp and SP
Programming
are disabled
EUHRUP
205
40
Selection or Range of Setting
Upper Display
English
Numeric
Enter a value within
the setpoint limits
DIS
ENAB
0 to 9999 in
Engineering units
per hour
UDC2500 Universal Digital Controller Product Manual
Code
SETPOINT RAMP FINAL SETPOINT—
Enter the value desired for the final setpoint.
The controller will operate at the setpoint set
here when ramp is ended.
ATTENTION If the ramp is on HOLD, the
held setpoint can be changed by the ▲ and ▼
keys. However, the ramp time remaining and
original ramp rate is not changed. Therefore,
when returning to RUN mode, the setpoint
will ramp at the same rate as previous to the
local setpoint change and will stop if the final
setpoint is reached before the time expires. If
the time expires before the final setpoint is
reached, it will jump to the final setpoint.
ATTENTION SP RAMP and SP RATE will
cause the SP portion of Accutune to abort.
PV Tune will continue to function normally.
Ramp is placed into HOLD while tuning
(TUNE configuration).
SETPOINT RATE—Lets you configure a
specific rate of change for any local setpoint
change.
0
DISABLE SETPOINT RATE—Disables the
setpoint rate option.
1
ENABLE SETPOINT RATE—Allows the SP
rate feature.
RATE UP—Rate up value. When making a
setpoint change, this is the rate at which the
controller will change from the original
setpoint up to the new one. The ramping
(current) setpoint can be viewed as SPn in
the lower display.
Entering a 0 will imply an immediate change
in Setpoint (i.e., no rate applies).
Parameter
Definition
4/07

Advertisement

Table of Contents
loading

Table of Contents