Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
High Output
000E
Limit
Low Output
000F
Limit
Output Deadband
0012
for Time Duplex
Output Deadband
0014
for TPSC
Output
0013
Hysteresis
Failsafe Mode
00D5
Failsafe Output
0028
Level
TPSC Power-up
00B7
Output
TPSC Failsafe
00B8
Output
Proportional
0094
Band Units
Reset Units
0095
PV High Range
0036
PV Low Range
0037
210
Register
Data
Address
Type
Hex
Decimal
014
FP
015
FP
018
FP
020
FP
019
FP
213
INT
040
FP
183
INT
184
INT
148
INT
149
INT
054
FP
055
FP
UDC2500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
–5 to 105% of output
R/W
–5 to 105% of output
R/W
–5 to +25.0%
R/W
0.5 to 5.0%
R/W
0.0 to 100.0% of PV
R/W
0 = Latching
1 = Non latching
R/W
0 to 100%
R/W
0 = Last
1 = Failsafe
R/W
0 = Motor goes to closed
position (0%)
1 = Motor goes to open
position (100%)
R/W
0 = Gain
1 = Proportional band
R/W
0 = Minutes
1 = RPM
R
PV High Limit
R
PV Low Limit