Table 9-4 Register Address Format For Function Code 21 - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

File Number
The file number word contains the register number from the register address structure
shown in Table 9-1 and Table 9-2. Although the register address structure tables indicate
up to 13 data registers are available for access, only register address 3 is currently
supported.
Register Address
The register address is used to designate the tag ID number for the parameter being
accessed. The register address is made up of two bytes—the MSB = 00 always. The LSB
contains the RS422 tag ID number. The tag ID numbers represent the parameter's
register address(es). See Section 10 for the tag ID numbers.

Table 9-4 Register Address Format for Function Code 21

Register
Address(es)
(Dec)
001 to 125
128 to 215
& 255
Unrestricted Registers
As mentioned previously, all register data is stored in the EEROM of this instrument with
some exceptions. These exceptions were made to allow write access to override
information. The registers, which are designated as Override values, are listed below.
These registers do not have restrictions on the number of writes.
ID Tag
125
Restrictions on Parameter Numbers in One Message
The maximum number of writeable parameters per write request is 1.
4/07
Register
Address(es)
(Hex)
0001 to 007D
analog formatted data
(2 registers – IEEE 32-bit floating point)
0080 to 00D7
integer formatted data
& 00FF
(2 registers – IEEE 32-bit floating point)
Register Number
(7Dh)
UDC2500 Universal Digital Controller Product Manual
Format
UDC Usage
Computer Setpoint
Modbus RTU Function Codes
187