Input 2 Set Up Wiring; Table 5-11 Set Up Wiring Procedure For 0 To 20 Ma Or 4 To 20 Ma Inputs - Input 2; Figure 5-8 Wiring Connections For 0 To 20 Ma Or 4 To 20 Ma Input - Input 2 - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Input Calibration

5.6 Input 2 Set Up Wiring

0 to 20 mA or 4 to 20 mA Inputs – Input 2
Refer to Figure 5-8 and wire the controller according to the procedure given in Table
5-13.
Table 5-11 Set Up Wiring Procedure for 0 to 20 mA or 4 to 20 mA Inputs –
Step
1
Connect the copper leads from the calibrator to the Input #2 terminals as shown in
Figure 5-8.
2
Place current source at zero before switching on.
3
Do not switch current source ON/OFF while connected to the instrument.
Figure 5-8 Wiring Connections for 0 to 20 mA or 4 to 20 mA Input – Input 2
146
+
+
Current
Current
Source
Source
_
_
UDC2500 Universal Digital Controller Product Manual
Input 2
Action
25+
25+
26 (no connection)
26 (no connection)
27-
27-
Copper Leads
Copper Leads
Equal Length
Equal Length
4/07