Algorithm; Table 10-12 Set-Up Group - Algorithm - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
10.7.4

Algorithm

Table 10-12 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Algorithm.
Parameter
Description
Control
0080
Algorithm
Selection
(Selection here will
affect ID code 160 in
Output Algorithms.)
Timer
00D8
Period
0063
Start (Initiation)
00D9
LDISP (Selection) 00DA 218
Timer Reset
00D6
Timer Increment
00D7
202
Table 10-12 Set-up Group – Algorithm
Register
Data
Address
Type
Hex
Decimal
128
INT
216
INT
099
FP
217
INT
INT
214
INT
215
INT
UDC2500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = ON/OFF
1 = PID-A
2 = PID-B
3 = PD-A with Manual
Reset
4 = Three Position Step
5 = Disable
R/W
0 = Disable
1 = Enable
R/W
00.00 TO 99.59
R/W
0 = Key (Run/Hold Key)
1 = Alarm 2
R/W
0 = TI REM
1 = Elapsed Time
R/W
0 = Key (Run/Hold Key)
1 = AL1 (Alarm 1 or Key)
R/W
0 = Min (Counts hr/min)
1 = Sec (Counts min/sec)
4/07

Advertisement

Table of Contents
loading

Table of Contents