Parameter
Description
Alarm 1 Setpoint 2
Type
Alarm 2 Setpoint 1
Type
Alarm 2 Setpoint 2
Type
Alarm 1 Setpoint 1
Event
Alarm 1 Setpoint 2
Event
Alarm 2 Setpoint 1
Event
Alarm 2 Setpoint 2
Event
Alarm Hysteresis
Alarm Latching for
Output 1
Alarm States
Alarm 1 Blocking
4/07
Modbus Read, Write and Override Parameters plus Exception Codes
Register
Address
Type
Hex
Decimal
008E
142
INT
0090
144
INT
0092
146
INT
008D
141
INT
008F
143
INT
0091
145
INT
0093
147
INT
0029
041
FP
00C8
200
INT
00C9
201
INT
00CA 202
INT
UDC2500 Universal Digital Controller Product Manual
Data
Access
R/W
Same as 140
R/W
Same as 140
R/W
Same as 140
R/W
0 = Low Alarm
1 = High Alarm
R/W
0 = Low Alarm
1 = High Alarm
R/W
0 = Low Alarm
1 = High Alarm
R/W
0 = Low Alarm
1 = High Alarm
R/W
0.0 to 100% of output or
span
R/W
0 = Non Latching
1 = Latching
R/W
State = 0 = Not in Alarm
State = 1 = In Alarm
Bit 0 = Alarm 11 State
Bit 1 = Alarm 12 State
Bit 2 = Alarm 21 State
Bit 3 = Alarm 22 State
Event = 0 = Low
Event = 1 = High
Bit 4 = Alarm 11 Event
Bit 5 = Alarm 12 Event
Bit 6 = Alarm 21 Event
Bit 7 = Alarm 22 Event
R/W
0 = Disable
1 = Block 1
2 = Block 2
3 = Block 1 2
Data Range or
Enumerated Selection
215