Output Calibration

6.4 Restore Output Factory Calibration Procedure

Introduction
The factory calibration constants for the Current and Auxiliary Outputs are stored in its
non-volatile memory. Thus, you can quickly restore the "Factory Calibration" for those
outputs by simply changing the CO RANGE or AO RANGE to the other setting and then
changing it back to the original type.
Refer to Table 6-5 Restore Factory Calibration for procedure
ATTENTION
A restored factory calibration overwrites any previous field calibration done for the output.
Protect your field calibration from accidental overwrites by configuring the appropriate
LOCKOUT selection after calibration.
See Section 3 - Configuration for specific instructions to set the lockout.

Table 6-5 Restore Factory Calibration Procedure

Step
Operation
1
Set LOCKOUT to
NONE
Enter OUTPUT
2
or OPTIONS
Setup Group
Scroll through
3
Functions
156
Press
until you see :
Setup
Setup
Upper Display = SET
Lower Display = TUNING
Until you see:
Function
Function
Function
Upper Display = one of the following:
NONE – all parameters are read/write
CAL – all parameters are read/write except Calibration
CONF – configuration parameters are Read Only; no writes
permitted
VIEW – Tuning and Setpoint Ramp parameters are
read/write. No other parameters can be viewed.
ALL – Tuning and Setpoint Ramp parameters are available
for read only. No other parameters can be viewed.
Lower Display = LOCK
Until NONE is in the upper display
or
until you see :
Setup
Setup
Upper Display = SET
Lower Display = OUTALG (for the Current Output)
- or -
Lower Display = OPTION (for the Auxiliary Output)
until you see :
Function
Function
Function
Upper Display = the current selection
Lower Display = CRANGE (for the Current Output)
- or -
Lower Display = ARANGE (for the Auxiliary Output)
to change the range configuration to the other selection
or
until the lower display rolls through the rest of the functions and
Function
Function
Function
returns to:
UDC2500 Universal Digital Controller Product Manual