Function Prompt
Lower Display
English
Numeric
Code
ALARM1
1114
BLOCK
1115
DIAGAL
1116
4/07
Selection or Range of Setting
Upper Display
English
Numeric
NO LAT
LATCH
DIS
AL1
AL 2
AL12
DIS
AL1
AL 2
DISWRN
UDC2500 Universal Digital Controller Product Manual
Code
LATCHING ALARM OUTPUT 1—Alarm
output 1 can be configured to be Latching or
Non-latching.
0
NO LAT—Non-latching
1
LATCH—Latching
ATTENTION When configured for latching,
the alarm will stay active after the alarm
condition ends until the RUN/HOLD key is
pressed.
ALARM BLOCKING—Prevents nuisance
alarms when the controller is first powered
up. The alarm is suppressed until the
parameter gets to the non-alarm limit or
band. Alarm blocking affects both alarm
setpoints.
DISABLE—Disables blocking
0
AL1—Blocks alarm 1 only
1
2
AL2—Blocks alarm 2 only
3
AL12—Blocks both alarms
ATTENTION When enabled on power up
or initial enabling via configuration, the alarm
will not activate unless the parameter being
monitored has not been in an alarm condition
for a minimum of one control cycle (167 ms).
DIAGNOSTIC—Monitors the Current Output
and/or Auxiliary Output for an open circuit
condition. If either of these two outputs falls
below about 3.5 mA, then an Alarm is
activated. This configuration is in addition to
whatever was selected for AxSxTYPE.
DISABLE—Disables Diagnostic Alarm
0
ALARM 1—Alarm 1 is diagnostic alarm
1
2
ALARM 2—Alarm 2 is diagnostic alarm
3
DISABLE WARNING—Disables Output Fail
message on lower display
Configuration
Parameter
Definition
81