Troubleshooting/Service
7.8 Restoring Factory Configuration
Introduction
This procedure restores the configuration of the instrument back to the Factory Settings
per Section 3.17.
ATTENTION: Restoring the factory configuration overwrites all user-entered
configuration changes. This procedure cannot be undone, it is a one-way process.
Table 7-15 explains how to restore Factory Configuration.
Step
Turn off the power to the instrument for at least five seconds.
1
2
Turn the power back on and simultaneously press the "FUNCTION" and
3
If step 2 was performed correctly, the instrument will now display "UDC"
[Upper] "UPDATE" [Lower].
4
Press the FUNCTION Key. The instrument will now display "DIS" [Upper]
"RESTORE" [Lower].
5
Press the
"RESTORE" [Lower].
6
Press the FUNCTION Key. The instrument will now display "DOIN"
"RESTORE"
When the instrument finishes the restore operation, it automatically resets
7
itself and restarts in the product mode. The instrument configuration will
now be the same as it was when the instrument left the factory and all user-
entered configurations since that time have been overwritten.
174
Table 7-15 Restoring Factory Configuration
keys. This must be done while "TEST DONE" is being displayed.
key. The instrument will now display "CFG" [Upper]
UDC2500 Universal Digital Controller Product Manual
What to do
4/07