Function Prompt
Lower Display
English
Numeric
Code
OUT Hi
811
OUT Lo
812
D BAND
813
HYST
814
FAILSF
815
FAILSF
816
4/07
Selection or Range of Setting
Upper Display
English
Numeric
0 % to 100 %
–5 % to 105 %
0 % to 100 %
–5 % to 105 %
–5.0 to 25.0 %
0.0 to 25.0 %
0.5 to 5.0 %
0.0 to 100.0 % of
PV
0 to 100 %
0
100
UDC2500 Universal Digital Controller Product Manual
Code
HIGH OUTPUT LIMIT—This is the highest
value of output beyond which you do not
want the controller automatic output to
exceed.
For relay output types.
For current output types.
LOW OUTPUT LIMIT—This is the lowest
value of output below which you do not want
the controller automatic output to exceed.
For relay output types.
For current output types.
DEADBAND is an adjustable gap between
the operating ranges of output 1 and output 2
in which neither output operates (positive
value) or both outputs operate (negative
value).
Time Duplex
On-Off Duplex
Three Position Step
HYSTERESIS (OUTPUT RELAY) is an
adjustable overlap of the ON/OFF states of
each control output. This is the difference
between the value of the process variable at
which the control outputs energize and the
value at which they de-energize.
ATTENTION Only applicable for ON/OFF
control.
FAILSAFE OUTPUT VALUE—The value
used here will also be the output level when
you have Communications SHED set to
failsafe or when NO BURNOUT is configured
and Input 1 fails.
ATTENTION Applies for all output types
except Three Position Step Control.
THREE POSITION STEP FAILSAFE
OUTPUT
0 PCT—Motor goes to closed position.
100 PCT—Motor goes to open position.
Configuration
Parameter
Definition
65