Function Prompt
Lower Display
English
Numeric
Code
A1S1EV
1103
A1S2TY
1104
A1S2VA
1105
A1S2HL
1106
A1S2EV
1106
A2S1TY
1107
A2S1VA
1108
4/07
Selection or Range of Setting
Upper Display
English
Numeric
BEGIN
END
Value in
engineering units
HIGH
LOW
BEGIN
END
Value in
engineering units
UDC2500 Universal Digital Controller Product Manual
Code
If Setpoint Programming is enabled and if
the Alarm Type is configured for Event
On/Off:
ALARM 1 SEGMENT EVENT 1—Select
whether you want the alarm type chosen in
prompt A1S1TYPE to alarm the beginning or
end of a segment in setpoint Ramp/Soak
programming.
0
BEGINNING OF SEGMENT
1
END OF SEGMENT
ATTENTION Alarms configured for events
will not operate on Setpoint Program
segments of zero length.
ALARM 1 SETPOINT 2 TYPE—Select what
you want Setpoint 2 of Alarm 1 to represent.
The selections are the same as A1S1TYPE.
ALARM 1 SETPOINT 2 VALUE—This is the
value at which you want the alarm type
chosen in prompt A1S2TYPE to actuate.
The details are the same as A1S1 VAL.
ALARM 1 SETPOINT 2 STATE—Same as
0
A1S1HL.
1
ALARM 1 SEGMENT EVENT 2—Same as
0
A1S1EV.
1
ALARM 2 SETPOINT 1 TYPE—Select what
you want Setpoint 1 of Alarm 2 to represent.
The selections are the same as A1S1TYPE.
ATTENTION Not applicable with Relay
Duplex unless using Dual Relay PWA.
ALARM 2 SETPOINT 1 VALUE—This is the
value at which you want the alarm type
chosen in prompt A2S1TYPE to actuate.
The details are the same as A1S1 VAL.
Configuration
Parameter
Definition