4. Set Up and Calibration Procedures - Calibration
Calibrate Input
The 10260S actuator accepts a variety of signal inputs.
1. 0 mA to 20 mA, or 4 mA to 20 mA
2. 0 Volts to 5 Volts, 1 Volt to 5 Volts, or 0 Volts to 10 Volts
The input type is selected through the Input set up group using the local keypad.
Refer to Figure 17 for the wiring connections and follow the procedure in Table 23 to calibrate the input
circuit of the 10260 S actuator.
ATTENTION
For an input calibration to be saved, you must complete the procedure. The calibration will not
be saved if you exit without completing the steps of the procedure.
To exit calibation mode, press DISPLAY or SETUP keys.
Step
Operation
1
Enter Calibration
Mode
2
Calibrate Zero (0%)
3
Calibrate Span
(100%)
4
60
10260S HercuLine® Actuator Installation, Operation and Maintenance Manual

Table 23 Input Calibration Procedure

Press
SETUP
Upper Display =
until you see
Lower Display =
FUNCTION
Upper Display =
Lower Display =
Upper Display =
or
key
Lower Display =
FUNCTION
Upper Display =
Lower Display =
Adjust the signal source to an output value equal
to 0% range value.
Wait 5 seconds, then go to step 3.
FUNCTION
Upper Display =
Lower Display =
Adjust the signal source to an output value equal
to 100% range value.
Wait 5 seconds, then go to step 4.
FUNCTION
Calibration for zero and span input values are now
saved. Input calibration is complete.
NOTE: . You may also exit calibration mode by
pressing the DISPLAY or SETUP keys.
Result
CAL
INPUT
DIS
CAL IN
BEGN
CAL IN
APLY
INZERO
APLY
INSPAN
Revision 5
7/07