Table 25 Input Calibration Procedure - Honeywell HercuLine 2000 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for HercuLine 2000 Series:
Table of Contents

Advertisement

Step
Operation
Enter Calibration
1
Mode
Calibrate Zero (0%)
2
Calibrate Span
3
(100%)
4
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/08

Table 25 Input Calibration Procedure

Press
SETUP
Upper Display =
until you see
Lower Display =
FUNCTION
Upper Display =
Lower Display =
Upper Display =
or
key
Lower Display =
FUNCTION
Upper Display =
Lower Display =
Adjust the signal source to an output value equal to 0% range
value.
Wait 5 seconds, then go to step 3.
FUNCTION
Upper Display =
Lower Display =
Adjust the signal source to an output value equal to 100%
range value.
Wait 5 seconds, then go to step 4.
FUNCTION
Calibration for zero and span input values are now saved. Input
calibration is complete.
NOTE: The display will automatically go to the CAL MOTOR set
up display. See Table 26. You may also exit calibation mode by
pressing the DISPLAY or SETUP keys.
ATTENTION:
When calibrating the motor to a short stroke range, you must
reset the end-of-travel limit switches. See Setting End-of-Travel
Limit Switches.
Set Up and Calibration Procedures
Result
CAL
INPUT
DIS
CAL IN
BEGN
CAL IN
APLY
INZERO
APLY
INSPAN
Calibration
69