11.13 Notes on the Parameters of the Analog Output Modules

Output
Type/Output
Range
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
You specify the output type by selecting the corresponding module type. For
each module type, you have the option of entering an output range of the pa-
rameters or value ranges listed below.
Table 11-5

Output Types/Output Ranges of the Analog Output Modules

Output Type
Output Range
Voltage
1 ... 5 V
10 V
Current
0 ... 20 mA
4 ... 20 mA
SC Analog Electronic Modules – Parameters
Notes
Wire the S+ and S– sense inputs of the modules
directly to the load to be driven in order to com-
pensate for line effects.