SC Analog Electronic Modules – Parameters
11.28 Analog Value Representation for Output Modules in S5 Number For-
mat
How to Read the
Measurement
Tables
Analog Value
Representation
Voltage Range
10 V
11-52
The tables in this section contain the measurement representations for the
individual measurement ranges of the analog output modules. The table val-
ues apply to all modules with the corresponding measurement ranges.
The following tables contain the digitized analog values for the various mea-
surement ranges.
Since the binary representation of the analog values is always the same, the
following tables contain only the measurement ranges against the units.
The following tables show the analog value representation for output chan-
nels in various voltage ranges.
System
Dec.
117.578 %
1204
117.578 %
1204
1025
100 %
1024
0.097 %
1
0 %
0
–0.097 %
– 1
– 100 %
– 1024
– 1025
– 117.578 %
– 1204
–117.578 %
–1204 0.00 V
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Voltage Range
10 V
0.00 V
Overflow, no voltage and no cur-
rent
11.76 V
Overrange
g
10 V
9.76 mV
0 V
Rated range
– 9.76 mV
– 10 V
Underrange
– 11.76 V
Underflow, no voltage and no cur-
rent
EWA 4NEB 780 6009-02c