Static Parameters Of The 2 Ai Rtd Electronic Module - Siemens Metro 21 M216KA Operator's Manual

Distributed i/o device
Table of Contents

Advertisement

SC Analog Electronic Modules – T echnical Data
Parameters
Table 12-9

Static Parameters of the 2 AI RTD Electronic Module

Parameter
Measurement type
Measurement range
Resistance measurement
with 4-conductor connec-
tion
Temperature measure-
ment with thermal resist-
ance
Interference frequency sup-
pression
Smoothing
Format
Default Parameters
12-46
The 1 AI RTD electronic module uses the following parameters:
Value Range
Deactivated
Resistance 0...600
Temperature measurement
with thermal resistance
Resistance 0...600
Pt100 climatic range
Pt100 standard range
Ni100 standard range
50 Hz (integration time 60
ms)
60 Hz (integration time 50
ms)
None
Weak
Medium
Strong
SIMATIC S7
SIMATIC S5
If you have not set the parameters of the 1 AI RTD electronic module using
the specified software (see Chapter 4), the default settings apply to both input
channels after a restart (see Table 12-9).
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Default Parameters
Resistance 0...600
Pt100 standard range
50 Hz
None
SIMATIC S7
EWA 4NEB 780 6009-02c