C.3.3
Configuration Frame Example
1st Example
Configuration
Frame for
Example 1
2nd Example
Configuration
Frame for
Example 2
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Configuration Frame and Parameterization Frame for the ET 200L
The following example describes the structure of a configuration frame of an
ET 200L-SC 16 DO DC 24V/0.5A with:
2 bytes DO
A Smart Connect with 2 electronic modules (SC): 2DI and 2DO
The configuration frame thus consists of the 25 bytes described below:
Configuration
Slot
Frame
04-00-00-AD-C4 1
04-00-00-9B-40
2
04-00-00-8F-C0
3
83-01-00-AF-48
4
C2-00-00-42-45
5
The following example describes the structure of a configuration frame of an
ET 200L-SC 16 DI/16 DO DC 24V/0.5A with:
2 bytes DI, 2 bytes DO
A Smart Connect with 4 digital electronic modules: 2 2DI and 2 2DO
and with 3 analog electronic modules: 1 2AI, 1 1AI and 1 1AO
The configuration frame thus consists of the following 30 bytes:
Configuration
Slot
Frame
04-00-00-AD-C4 1
04-00-00-9B-40
2
04-00-00-8F-C0
3
C2-01-01-AF-48
4
C2-01-01-42-45
5
C2-40-42-42-45
6
Meaning
Virtual slots
2 bytes DO
Smart Connect with electronic modules (SC): 2DI, 2DO.
The inputs and outputs of the 2DI/2DO are distributed
over 1 input and 1 output byte.
Meaning
Virtual slots
2 bytes DO / 2 bytes DI
SC with digital electronic modules: 2 2DI and
2 2DO. The inputs and outputs of the 2 2DI/2 2DO
are distributed over 2 input and 2 output bytes.
SC with analog electronic modules: 1 2AI, 1 1AI and
1 1AO. The inputs and outputs are distributed over 3
input words and 1 output word.