ET 200L Electronics Blocks – Technical Data
Voltages, Currents, Potentials
Rated supply voltage for
electronics (4L+, 5L+)
Reverse polarity
protection
Power failure with-
stand time
Rated load voltage
(1L+, 2L+ and 3L+)
Aggregate current of outputs (per byte)
Horizontal installation
Up to 30 C
Up to 40 C
Up to 60 C
All other installation
positions
Up to 40 C
Galvanic isolation
Between channels
Between channels and
PROFIBUS-DP
Insulation tested with
Power input
from supply voltage
L4+/L5+
from load voltage L1+
and L2+/L3+ (without
load)
Power loss of module
Status, Interrupts, Diagnostics
Status display
Interrupts
Diagnostic function
Bus monitoring
PROFIBUS-DP
Monitoring of electro-
nics power supply
8-8
24 V DC
Yes
At least 20 ms
24 V DC
Max. 4 A
Max. 3 A
Max. 2 A
Max. 2 A
No
Yes
500 V DC
Max. 70 mA
Max. 50 mA per load
group
Typically 5 W
Green LED per channel
None
Yes
Red "BF" LED
Green "ON" LED
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Actuator Selection Data
Output voltage
At signal "1"
Output current
At signal "1"
Rated value
Permissible range
At signal "0"
(residual current)
Output delay (with resistive load)
With "0" after "1"
With "1" after "0"
Load resistance range
Lamp load
Parallel connection of two outputs
For redundant control
of load
For performance im-
provement
Driving a digital input
Switching frequency
Resistive load
Inductive load to
IEC 947-5-1, DC13
Lamp load
Limitation of voltage in-
duced on circuit interrup-
tion
Short-circuit protection
Response threshold
At least L1+ (– 3 V) or
L2+/L3+ (3 V)
0.5 A
1 mA to 0.5 A
Max. 1 mA
Max. 50 s
Max. 200 s
41
to 28 k
Max. 5 W
Possible (outputs in same
group only)
Not possible
Possible
Max. 100 Hz
Max. 0.5 Hz
Max. 8 Hz
Typically L1+ (– 55 V) or
L2+/L3+ (– 55 V)
Yes
Typically 0.7 A
EWA 4NEB 780 6009-02c