SC Analog Electronic Modules – Parameters
Voltage Range
1...5 V
Current range
0...20 mA and
4...20 mA
11-40
Measured
System
Value in %
Dec.
Hex.
118.5149 %
32767
7FFF
117.593 %
32512
7F00
117.589 %
32511
7EFF
27649
6C01
100 %
27648
6C00
0.003617 %
1
1
0 %
0
0
– 1
FFFF
– 25 %
– 6912
E500
– 6913
E4FF
117.593 %
– 32512
8100
- 117.596 %
– 32513
80FF
– 118.519 %
– 32768
8000
System
Dec.
Hex.
118.5149 %
32767
7FFF
117.593 %
32512
7F00
117.589 %
32511
7EFF 23.52 mA
27649
6C01
100 %
27648
6C00
0.003617 %
1
1
0 %
0
0
– 1
FFFF 0 mA
– 25 %
– 6912
E500
– 6913
E4FF 0 mA
– 117.593 %
– 32512 8100
- 117.596 %
– 32513 80FF
– 118.519 %
– 32768 8000
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Voltage Range
1 ... 5 V
Overflow, no voltage and no
0.00 V
current
current
0.00 V
5.70 V
Overrange
g
5 V
Rated range
1V+144.7 V
1 V
Underrange
g
1V-144.7 V
0 V
Impossible; output value
p
0.00 V
restricted to 0 V
restricted to 0 V
0.00 V
0.00 V
Underflow, no voltage and no
current
current
0.00 V
Current range
0 ... 20 mA
4 ... 20 mA
0.00 mA
0.00 mA
22.81 mA
20 mA
20 mA
723.4 nA
4mA+578.7 nA
0 mA
4 mA
4mA-578.7 nA
0 mA
0 mA
0 mA
0 mA
0 mA
0 mA
0 mA
0 mA
0 mA
EWA 4NEB 780 6009-02c
g
p
g
Overflow, no
voltage and no
voltage and no
current
Overrange
g
Rated range
Underrange
g
Impossible;
output value
output value
restricted to 0 mA
Underflow, no
voltage and no
voltage and no
current

Hide quick links: