Siemens Metro 21 M216KA Operator's Manual page 305

Distributed i/o device
Table of Contents

Advertisement

Analog value formation
Measurement principle
Integration and conversion time/
resolution per channel
Parameterized
Integration time in ms
Conversion time in ms
Cycle time in ms
Resolution (incl. overrange/rep-
resentation in two's complement)
0...600
Pt100 climatic
Pt100 standard
Ni100 standard
0...600
Pt100 climatic
Pt100 standard
Ni100 standard
Interference voltage suppres-
sion for interference fre-
quency f1 in Hz
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
SC Analog Electronic Modules – T echnical Data
integrative
Input ranges (rated values)/input
resistance
yes
50
60
110
130
110
130
Permitted input voltage
for resistance measurement input
and constant current inputs/out-
puts (destruction limit)
S7 format
14 bits
Connection of sensors
0.1 C/digit
For resistance measurement
0.1 C/digit
with
0.1 C/digit
S5 format
13 bits
Characteristic curve linearization yes; parameterized
0.05 C/digit
0.5 C/digit
0.5 C/digit
Temperature compensation
Smoothing of measured values
50
60
Sensor Selection Data
0...600
Pt100 (climatic; -120...+130 C) / >1 M
Pt100 (standard; -200...+850 C) / >1 M
Ni100 (standard; -60...+250 C) / >1 M
max.10 V perma-
nent;
25 V for max. 1 s
(pulse duty factor
1:20)
4-conductor connection
yes; with compensa-
tion of the line re-
sistances
For Pt100 to DIN IEC 751
For Ni100 to DIN 43760
no
yes; set by parame-
ters in 4 steps by
digital filtering
Step
Time constant
None
1x cycle time
Weak
8x cycle time
Medium
64x cycle time
Strong
128x cycle time
/ >1 M
12-49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents