Siemens Metro 21 M216KA Operator's Manual page 235

Distributed i/o device
Table of Contents

Advertisement

Voltage
Measurement
Range 1...5 V
Current
Measurement
Range
20 mA
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Measured
System
Value in %
Dec.
Hex.
117.589 %
32767
7FFF
117.589 %
32511
7EFF
27649
6C01
100.000 %
27648
6C00
0.003617 %
1
1
0 %
0
0
– 1
FFFF
–17.593 %
– 4864
ED00
–17.593 %
32767
7FFF
Measured
System
Value in %
Dec.
117.589 %
32767
117.589 %
32511
27649
100.000 %
27648
0.003617 %
1
0 %
0
– 0.003617 %
– 1
– 100.000 %
– 27648
– 27649
– 117.593 %
– 32512
–117.593 %
– 32768
SC Analog Electronic Modules – Parameters
Voltage Measurement Range
1 ... 5 V
5.704 V
Overflow
5.704 V
Overrange
5 V
Rated range
1 V + 144.7 V
1 V
Underrange
0.296 V
0.296 V
Open circuit
Current Measurement Range
Hex.
20 mA
7FFF
23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
1
723.4 nA
0
0 mA
FFFF
– 723.4 nA
9400
– 20 mA
93FF
8100
– 23.52 mA
8000
– 23.52 mA
Overflow
Overrange
g
Rated range
Underrange
g
Underflow
11-33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents