NOTE → Strobe synchronization is not available when the PAD-5 NAC Follower Input is
3.2.3
NOTE→ The battery charger has priority over the total system current. If the batteries
3.2.3.1
2 Combined Total output between all on-board NACs, Class A Expansion Module NACs, and AUX is 9A for a FP2012-U1 (300
Watt Power Supply) and 6A for a FP2011-U1 (170 Watt Power Supply).
28
Siemens Industry, Inc.
Smart Infrastructure

X600 NAC Follower

connected to a Fire Alarm Control Panel with full-wave rectified output.
Pin
Designation Description
1,3
BF (-)
Input from external fire control panel and voice alarm fire control panel.
The return feed from the external control unit's NAC circuit connects here.
2,4
BF (+)
Input from external fire control panel and voice alarm fire control panel.
The active positive output from the external control unit's NAC circuit
connects here.
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG

Dedicated Auxiliary Output (X800)

The dedicated Auxiliary Output has a maximum output current of 3A
can be used for devices such as door holders, DACT, or RDT. The output is power
limited and supervised for overcurrent and direct shorting. To configure the output to
shut down during AC loss to conserve battery, the Zeus configuration tool must be
used.
If the output is configured to turn off on battery, then the output is used for
supplementary purposes only.
are drained, more current needs to go to charging the batteries. Therefore, if
the NACs are configured as Auxiliary Outputs, they will be turned off while the
batteries charge. The OI will display an overcurrent condition. After the
batteries make it to float, the trouble will go out and the Auxiliary Outputs will
return to ACTIVE. The dedicated Auxiliary Output (X800) will remain on, even
if the battery charger is active. It is only NACs configured for Auxiliary Output
that are affect by the battery charger priority.

Wiring the Dedicated Auxiliary Output

X800 Pins 3 and 4 are connected internally to Pins 1 and 2 respectively and are
used for ease tapping the output power to internal or external devices. Faults on
any terminal can affect all devices connected on 1,2 and 3,4.
X1001
X800
AUX
AUX
AUX
AUX
+
1
-
2
+
3
-
4
2
. The output
A6V101030358_en--_c