Siemens Metro 21 M216KA Operator's Manual page 324

Distributed i/o device
Table of Contents

Advertisement

The 1COUNT40kHz Counter Module
Behavior of the
Output
Output disabled
The output remains deactivated and is not affected by the events comparison value, zero-
crossing, overflow or underflow.
Active from compar-
ison value to over-
flow
*
The output is activated when the counter is in the range between the comparison value n and
overflow. When the counter is set to a value between comparison value and overflow, the
output is activated.
Active from compar-
ison value to under-
flow
*
The output is activated when the counter is in the range between the comparison value n and
underflow. When the counter is set to a value between comparison value and underflow, the
output is activated.
Active at comparison
value counting up-
ward
*
The output is activated for the length of the pulse duration when the comparison value is
reached counting upward.
Active at comparison
value counting
downward
*
The output is activated for the length of the pulse duration when the comparison value is
reached counting downward.
Active at comparison
value counting up-
ward/downward
Underflow Comparison value Overflow
The output is activated for the length of the pulse duration when the comparison value is
reached regardless of the direction of counting.
13-10
You can set one of 6 possible responses for the output when the comparison
value is reached. The alternatives are shown in the table below.
Behavior of the Output
Underflow
Underflow
Underflow
Underflow
Underflow
Upward
t
* Note the conditions overleaf
= output active
t = pulse duration
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Comparison value
Overflow
Comparison value
Overflow
Comparison value
Overflow
t
Comparison value
t
Comparison value
Overflow
t
Underflow Comparison value Overflow
Overflow
Downward
EWA 4NEB 780 6009-02c