Siemens Metro 21 M216KA Operator's Manual page 201

Distributed i/o device
Table of Contents

Advertisement

Technical Data
Dimensions and Weight
Dimensions W H D (mm)
Weight
Module-Specific Data
Number of outputs
Contact type
Cable length
Unshielded
Shielded
Voltages, Currents, Potentials
Rated supply voltage of relay
L+
Reverse polarity protection
Galvanic isolation
Between channels and SC
bus
Between channel and supply
voltage of the relay
Permissible potential difference
Between ground and supply
voltage of the relay
Between ground or supply
voltage of the relay and the
output
Isolation tested with
Between ground and supply
voltage of the relay
Between ground or supply
voltage of the relay and the
output
Power input
From supply voltage L+
Power loss of the module
Status, Interrupts, Diagnostics
Status indication
Interrupts
Diagnostic functions
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The technical data of the 1DORel.AC230V digital electronic module is listed
below.
10 64 51
approx. 30 g
1
1 x A
max. 600 m
max. 1000 m
DC 24 V
yes
yes
yes
DC 75 V, AC 60 V
AC 240 V
AC 1500 V
DC 2500 V
max. 15 mA
typ. 0.7 W
green LED
none
none
SC Digital Electronic Modules – Technical Data
Actuator Selection Data
Continuous thermal current
Minimum load current
Switching capacity and lifetime
of the contacts
For resistive load
For inductive load in accor-
dance with
IEC 947-5-1 DC13/AC15
Lamp load
Internal contact connection
Parallel switching of 2 outputs
For redundant control of a
load
For performance enhance-
ment
Controlling a digital input
Switching frequency
Mechanical
With resistive load
With inductive load in accor-
dance with IEC 947-5-1
DC13/AC15
With lamp load
max. 5 A
1 mA
see Table 10-1
see Table 10-1
see Table 10-1
see Table 10-1
Varistor
rated voltage 275 V
possible
not possible
possible
max. 10 Hz
max. 1 Hz
max. 1 Hz
max. 0.1 Hz
max. 0.1 Hz
10-19