Siemens Metro 21 M216KA Operator's Manual page 155

Distributed i/o device
Table of Contents

Advertisement

Technical data
Dimensions and Weight
Dimensions
W
H
D (mm)
Weight
Module-Specific Data
Baud rate
Bus protocol
SYNC compatibility
Number of outputs
I/O Cable length
Unshielded
Shielded
Manufacturer ID
Voltages, Currents, Potentials
Supply voltage L1
Rated voltage
Permissible range
Frequency
Power failure
withstand time
Aggregate current of outputs (per point)
Horizontal installation
up to 40 C
up to 60 C
All other installation
positions
up to 40 C
Optical isolation
Between channels
Between L1 and
PROFIBUS-DP
Between channels and
PROFIBUS-DP
Insulation tested with
Power input
from supply voltage L
Power loss of module
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The following table shows the technical data of the L 16 DO AC 120 V/1.0 A
electronics block.
191
61
85.5
Approx. 294 g
9.6; 19.2; 93 .75; 187.5;
500, 1 500, 3000, and
6000 kBaud
PROFIBUS-DP
Yes
16
Max. 600 m
Max. 1000 m
0028
H
120 VAC
74 to 132 VAC
47 to 63 Hz
At least 20 ms
Max. 1 A
Max. 0.4 A
Max. 0.4 A
Yes
Yes
Yes
1500 VAC
Max. 170 mA
Typically 18.9 W
ET 200L Electronics Blocks – Technical Data
Status, Alarms, Diagnostics
Status display
Alarms
Diagnostic function
Bus monitoring
PROFIBUS-DP
Monitoring of
electronics
power supply
Actuator Selection Data
Load voltage L
Rated voltage
Permissible range
Frequency
Output voltage
With signal 1
Output current
With signal 1
Rated value
Permissible range
With signal 0
(residual current)
Zero cross inhibit voltage
Output delay
(with resistive load)
Size of motor starter
Up to 40 C
Up to 60 C
Lamp load
Parallel connection of two outputs
For redundant control
of load
For performance
improvement
Driving a digital input
Switching frequency
Resistive load
Inductive load
Lamp load
Short-circuit protection
Green LED per channel
None
Yes
Red "BF" LED
Green "ON" LED
120 VAC
74 to 132 VAC
47 to 63 Hz
At least L (– 1.5V)
1.0 A Pilot Duty
0.1 to 1.0 A
Max. 2.6 mA
Max. 60 V
Max. 20 ms
Max. size 4 acc. to NEMA
Max. size 3 acc. to NEMA
Max. 50 W
Possible
Not possible
Possible
Max. 10 Hz
Max. 0.5 Hz
Max. 1 Hz
No
8-23