Configuration Frame and Parameterization Frame for the ET 200L
3rd Example
Configuration
Frame for
Example 3
4th Example
Configuration
Frame for
Example 4
C-12
The following example describes the structure of a configuration frame of an
ET 200L-SC 32 DI DC 24V with:
4 bytes DI
No Smart Connect
The configuration frame thus consists of the 20 bytes described below:
Configuration
Slot
Frame
04-00-00-AD-C4 1
04-00-00-9B-40
2
04-00-00-AF-C0
3
43-03-00-9F-41
4
Note
You must always transfer the complete configuration frame to the
ET 200L-SC.
If you have not inserted a Smart Connect module, a configuration frame
is not sent for the SC section (slots 5 and 6).
The following example describes the structure of a configuration frame of an
ET 200L-SC IM-SC with:
A Smart Connect with 7 digital electronic modules: 4 2DI and 3 2DO
and with 6 analog electronic modules: 1 2AI, 2 1AI and 3 1AO
The configuration frame thus consists of the 25 bytes described below:
Configuration
Slot
Frame
04-00-00-AD-C4 1
04-00-00-9B-40
2
04-00-00-8F-C0
3
C2-04-03-42-4A
4
C2-48-44-42-4A
5
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Meaning
Virtual slots
4 bytes DI
Meaning
Virtual slots
SC with digital electronic modules: 4 2DI and
3 2DO. The inputs and outputs are distributed over
4 input and 5 output bytes.
SC with analog electronic modules: 1 2AI, 2 1AI and
3 1AO. The inputs and outputs are distributed over
5 input and 9 output words.
EWA 4NEB 780 6009-02c