g
Diagnostics
5.2.3
Structure of Station Statuses 1 to 3, Master Station Number and
Manufacturer Identification
Definition of
Station Status
Structure of
Station Status 1
Table 5-4

Structure of Station Status 1 (Byte 0)

Bit
Meaning
0
1: The DP slave cannot be addressed by
the DP master.
1
1: The DP slave is not yet ready to
exchange data.
2
1: The configuration data sent by the DP
master to the DP slave do not agree
with the installation of the DP slave.
3
1: An external diagnosis exists.
4
1: The requested function is not supported
by the DP slave.
5
1: The DP master cannot interpret the
reply from the DP slave.
6
1: The DP slave type does not agree with
the software configuration.
7
1: Parameters have been assigned to the
DP slave by a different DP master from
that which currently has access to the
DP slave.
5-8
Station statuses 1 to 3 provide an overview of the status of a DP slave (refer
to Figure 5-1, bytes 0 to 2).
Station status 1 provides information about the DP slave and is structured as
follows:
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
Action
Correct PROFIBUS address set on ET 200L?
Bus connector connected?
Voltage at DP slave?
RS 485 repeater set correctly?
Supply voltage ON/ OFF performed on
ET 200L?
Wait, because the ET 200L is just being pow-
ered up.
Correct station type or correct installation of
the ET 200L entered in the system configura-
tion software?
Check the contents of the external diagnosis.
Check the configuration.
Check the bus installation.
Correct station type entered in the system con-
figuration software?
The bit is always 1 if you are in the process of
accessing, for example, the ET 200L with the
PU or another DP master.
The PROFIBUS address of the parameteriza-
tion master is located in the "master
PROFIBUS address" diagnostic byte.
EWA 4NEB 780 6009-02c