2 Installing Hardware for the G700 Media Gateway and S8300 Media Server: Installation and Cabling
3.
Measure the AC voltages in the following order:
If the voltage readings do not measure the values given, the AC outlet is improperly wired. DO NOT
INSTALL THE SYSTEM. Advise the customer to have a licensed electrician correct the problem.
You are now ready to power the system.

Plug in AC Power

Once the ground and voltages have been verified to be correct for the installation, connect to AC power.
Plug the power cord into the outlet that was tested.
1.
Note: There is no On/Off power switch on the G700 Media Gateway. The AC inlet
serves as the disconnect device. To disconnect power from the G700 Media
Gateway, remove the power cord plug from the AC inlet.
The G700 Media Gateway will power up. The LEDs on the media modules, the S8300 Media
Server, and the G700 Media Gateway will flash at power-up. Each element will conduct a series
of self-tests.
2.
The LEDs on the G700 LED panel will flash, and the red ALM LED will light up until the self-
tests on the G700 Media Gateway have completed.
3.
The LEDs on the S8300 Media Server will light as described in the following sequence:
a . ALM - RED - lights up, then turns off
b . TEST - GREEN – lights up, then turns off
c . ACTIVE - YELLOW – lights up, then turns off
d . OK To REMOVE - GREEN - lights up, then turns off
e . LEFT LED in SERVICES port - GREEN (10 MB link speed) lights up, then turns off
f . LEFT LED in SERVICES port - YELLOW (100 MB link speed) lights up, then turns off
g . RIGHT LED in SERVICES port - GREEN lights up, then turns off
When you first power up the S8300, the red Major Alarm LED will be lit. During startup, self-
tests will run, after which all LEDs will be off. At this point, you can connect to the S8300. There
will be another flash of LEDs when Communication Manager starts.
86
1. Phase to neutral should be 110 to 125 V AC.
2. Neutral to ground should be less than 1 V AC.
3. Phase to ground should be 110 to 125 V AC.
Installation and Upgrades for G700 with S8300 or S8700
555-234-100 — Issue 3 — May 2003