The following is a setting example for a 200-V class Inverter with an input voltage of 230 V.
Key sequence
10 times
3 times
Setting the Power Supply Voltage Short Pin (400-V Class Inverter of
18.5 kW or More)
Set the power supply voltage short pin when setting the parameter (E1-01). Insert the short pin into the
voltage connector nearest to the actual power supply voltage.
It is factory-set to the 440-V connector when shipped.
Note 1. The above figure is the 400-V class Inverter (18.5 to 45 kW).
Note 2. Be sure to turn off the power supply switch and wait for at least one minute (three minutes for
models larger than 30 kW) before removing the front panel and setting the pin.
Display
Displays initialize mode.
Displays program mode.
Puts the Unit in program mode.
Displays the input voltage setting display.
Press to change data. (The leading digit will flash).
Causes the + to flash.
Set to "3"
The set values are overwritten. "Entry Accepted" is
displayed for approximately 0.5 seconds.
Returns to the input voltage display. Check that the
data has been updated.
Returns to the program mode display.
380 V
400/415 V 440 V
Explanation
460 V
Chapter 4
4-7