Advanced Operation
The sign bit is used as a data bit, so only positive (plus) data can be set.
The second digit below the decimal point is set by bits 8x10
made in units of 0.02 Hz. (If these three bits are "111," "110," and "101," they will be recognized as "9.")
H Setting an Analog Monitor Card (F4)
When using a 3G3IV-PAO08/PAO12 Analog Monitor Card, set the monitor items and gain with the fol-
lowing parameters. Parameters F4-02, F4-04, F4-05, and F4-06 can be changed during operation,
while F4-01 and F4-03 cannot.
Parameter
Display name
p y
number
F4-01
AO Ch1 Select
F4-02
AO Ch1 Gain
F4-03
AO Ch2 Select
F4-04
AO Ch2 Gain
F4-05
AO Ch1 Bias
F4-06
AO Ch2 Bias
Set parameters F4-01 and F4-03 (AO Ch1 Select and AO Ch2 Select) to the right side of the of "U1"
parameters in the table on page 3-12 of this manual. The setting range is between 1 and 38, but the
following numbers cannot be set: 4, 10, 11, 13, 14, 25, 28, 29, 30, 31, 34, 35.
Set the parameters F4-05 and F4-06 (AO Ch1 Bias and AO Ch2 Bias) to a bias that moves the output
characteristics up and down in parallel in 1% increments based on 10 V as 100%.
When the 3G3IV-PAO12 is used, outputs of 0 to 10 V are possible. For that, set parameter H4-07 (mul-
ti-function analog output signal level selection) to "1" (0 to 10-V outputs). There are some monitor
items, however, that can only use outputs of 0 to +10 V even if parameter H4-07 is set to "1."
When the 3G3IV-PAO08 is used, only outputs of 0 to +10 V are possible regardless of the parameter
H4-07 setting.
H Setting a Pulse Monitor Card (F7)
When using a 3G3IV-PPO36F Pulse Monitor Card, set the number of output pulses with parameter
F7-01.
Parameter
Display name
p y
number
F7-01
PO-36F
Selection
Setting
g
Units
Default
range
setting
0 to 38
---
2
0.00 to
Multi-
1.00
2.50
ple
0 to 38
---
3
0.00 to
Multi-
0.50
2.50
ple
–10.0 to
%
0.0
10.0
–10.0 to
%
0.0
10.0
Setting
g
Units
Default
range
setting
0 to 4
---
1
0
0
0
, 4x10
, and 2x10
Valid access levels
V/f
V/f with
Open Loop
Control
PG
Basic or Advanced
Basic or Advanced
Basic or Advanced
Basic or Advanced
Basic or Advanced
Basic or Advanced
Valid access levels
V/f
V/f with
Open Loop
Control
PG
Basic or Advanced
Chapter 6
, so the settings are
Flux
Vector
Vector
Flux
Vector
Vector
6-73