Installation
3G3FV-B2185 to B2220, B4185 to B4450
3-phase 200 VAC
(400 VAC)
3G3FV-B2300 to B2550
3-phase 200 VAC
Note 1. For 200-V class, 30 to 75 kW (B2300 to B2750-E) and 400-V class, 55 to 300 kW (B4550 to
B430K), input the control circuit power supply from r–s. (For others, create the control power
supply internally from the main circuit DC power supply.)
Note 2. The r–L1 (R) and s–L2 (S) terminals are short-circuited for shipping.
L1 (R)
T1 (U)
L2 (S)
T2 (V)
L3 (T)
T3 (W)
(See note 2)
Note: The DC reactor is built in.
L1 (R)
T1 (U)
L2 (S)
T2 (V)
L3 (T)
T3 (W)
(See note 1)
(See note 2)
Note: The DC reactor is built in.
Braking Resistor Unit (optional)
Braking Unit (optional)
Braking Resistor Unit (optional)
Braking Unit (optional)