Specifications; Protective Functions - Omron SYSDRIVE 3G3FV User Manual

High-function general-purpose inverter
Table of Contents

Advertisement

Specifications

Control Characteristics
A2004
A2007
Model number
3G3FV-
Power supply
DC reactor (option) connection possible.
harmonic
countermea-
sures
Control meth-
Sine wave PWM (high-carrier frequency control)
od
Carrier fre-
0.4 to 15 kHz (2.0 to 15 kHz in vector control)
quency
Speed control
1:100 (1:1000 with PG)
range
Speed control
0.2% ( 0.02% with PG)
precision
Speed control
5 Hz (30 Hz with PG)
response
Torque charac-
150% at 1 Hz (150% at 0 rpm with PG). A torque limit function is incorporated.
teristics
Torque control
5% (with PG)
precision
Torque control
40 Hz (with PG)
response
Frequency
0.1 to 400 Hz
control range
Frequency pre-
Digital references:
cision
Analog references:
(temperature
characteris-
tics)
Frequency set-
Digital references:
ting resolution
Analog references:
Output fre-
0.001 Hz
quency resolu-
tion
Overload
150% of rated current for one minute
capacity
Frequency set-
0 to 10 VDC (20 k ), 0 to 10 VDC (20 k ) voltage input or 4 to 20 mA (250 ) current input
ting signal
Acceleration/
0.01 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Deceleration
time
Braking torque
Approximately 20% (Increment possible with an external braking resistor.)
Voltage/fre-
Select vector control, one from 15 types of fixed V/f patterns, or set a user V/f pattern.
quency charac-
teristics

Protective Functions

Model number
A2004
A2007
3G3FV-
Motor protec-
Protection by electronic thermal.
tion
Instantaneous
Stops at approx. 200% of rated output current.
overcurrent
protection
Overload
Stops in one minute at approx. 150% of rated output current.
protection
Overvoltage
Stops when main-circuit DC voltage is approx. 410 V.
protection
Undervoltage
Stops when main-circuit DC voltage is approx. 190 V.
protection
Momentary
Stops for 15 ms or more. By selecting the momentary power interruption mode, operation can be continued if power is
power inter-
restored within 2 s.
ruption com-
pensation
(selection)
Cooling fin
Protection by thermistor.
overheating
A2015
A2022
A2037
A2055
0.01% (–10 to 40 C)
0.1% (25 10 C)
0.01 Hz (Less than 100 Hz), 0.1 Hz (100 Hz or higher)
0.03 Hz/60 Hz (11 bits + sign)
A2015
A2022
A2037
A2055
A2075
A2110
A2150
B2185
DC reactor built in
A2075
A2110
A2150
B2185
Chapter 9
B2220
B2300
B2370
B2450
0.4 to 10 kHz (2.0 to 10 kHz in vector
control)
B2220
B2300
B2370
B2450
B2550
B2750
-E
B2550
B2750
-E
9-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents