Omron SYSDRIVE 3G3FV User Manual page 338

High-function general-purpose inverter
Table of Contents

Advertisement

Parameter Lists
Para
Para
Name
meter
meter
Display
No.
No.
name
L8-02
Sets the detection temperature
Inverter
overheat
for the Inverter overheat
detection pre-alarm in C.
detection
pre-alarm
Note: The pre-alarm detects
level
OH
Pre-Alarm
Lvl
L8-03
Operation
Sets the operation for when the
Inverter overheat pre-alarm
after
Inverter
goes ON.
0: Ramp to stop in
overheat
pre-alarm
deceleration time C1-02.
1: Coast to stop
2: Fast stop in fast-stop time
C1-09.
C1 09.
3: Continue operation (Monitor
OH
display only.)
Pre-Alarm
Note: A fault will be given in set-
Sel
L8-05
0: Disabled
Input
open-phase
1: Enabled (Detects if input
current open-phase, power
protection
selection
supply voltage imbalance or
main circuit electrostatic
main circuit electrostatic
Ph Loss In
capacitor deterioration
Sel
occurs.)
L8-07
Output
0: Disabled
1: Enabled (Output open
open-phase
protection
phase detected at less than
5% of Inverter's rated
selection
current.)
Note: Output open phase may
Ph Loss
Out Sel
L8-10
Ground
0: Disable ground fault
fault
protection.
1: Enable ground fault
protection
selection
protection.
Ground
Fault Sel
7-50
Description
Description
Setting
Setting
50 to
130
when the cooling fin tem-
when the cooling fin tem-
perature reaches the set
value.
0 to 3
ting 0 to 2 and a minor
fault will be given in set-
ting 3.
0, 1
0, 1
y
be detected inadvertently
be detected inadvertently
when applied motor ca-
pacity is small for Inverter
capacity. In this case, set
to 0 (Disabled.)
0, 1
Default
Default
Chan-
Chan-
range
range
setting
setting
ges
ges
during
during
opera-
opera-
tion
tion
95
NO
A
3
NO
A
0
NO
A
0
NO
A
1
NO
A
Chapter 7
Control mode
V/f
V/f
Open
control
with
loop
PG
vector
A
A
A
A
A
A
A
A
A
A
Page
Page
Flux
vector
A
6-109
A
6-109
A
6-109
A
6-110
A
6-110