Fdna-01 Configuration Parameters - Group C (Group 3) - ABB FDNA-01 User Manual

Devicenet adapter module
Table of Contents

Advertisement

48 Start-up
FDNA-01 configuration parameters – group C (group 3)
Note: The actual parameter group number depends on the drive
type. Group C (group 3) corresponds to:
parameter group 54 in ACS355
parameter group 52 in ACSM1, ACS850 and ACQ810
parameter group 52 in ACS880 if the adapter is installed as
fieldbus adapter A or group 55 if the adapter is installed as
fieldbus adapter B.
1)
No.
Name/Value
01
DATA IN 1
(drive to master)
ACS355:
FBA DATA IN 1
ACSM1:
FBA DATA IN1
ACS850/ACQ810/
ACS880:
FBA data in1
0
101...9999
02...
DATA IN 2...
10
DATA IN 10
1)
The number of parameters in this group may vary by drive type and drive firmware.
Description
In input assembly instances that include drive
parameters, this parameter specifies which
parameter's value is placed in location DATA IN
1 value sent by the drive to the DeviceNet
network. Content is defined by a decimal
number in the range of 0 to 9999 as follows:
0
Not used
1...99 Virtual address area of drive control.
Not used with the FDNA-01 module.
101...
Parameter area of the drive
9999
Note: The FDNA-01 configuration parameters
are 16-bit parameters. If the mapped parameter
is a 32-bit parameter, it automatically reserves
two consecutive parameters. For example,
mapping a 32-bit parameter to parameter no. 1
also reserves parameter no. 2.
Not used
Parameter index with format xxyy, where xx is
the parameter group number (1...99) and yy is
the parameter number index within that group
(01...99).
See parameter
DATA IN
1.
Default
0
0