FENA-01/-11-/21 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
parameter group 51 in ACS355, ACS380, ACSM1, ACS480,
ACS580, ACS850 and ACQ810.
parameter group is typically 51/54 (group 151/154 in some
variants) in ACS880 and ACS880-M04 if the adapter is
installed as fieldbus adapter A/B.
No.
Name/Value
01
FBA type
02
Protocol/Profile
0 = MB/TCP ABB C
1 = MB/TCP ABB E
2 = MB/TCP T16
3 = MB/TCP T32
4 = MB/UDP ABB C Modbus over UDP: ABB Drives profile - Classic
5 = MB/UDP ABB E
6 = MB/UDP T16
7 = MB/UDP T32
03
Commrate
0 = Auto
1 = 100 Mbps FD
2 = 100 Mbps HD
3 = 10 Mbps FD
4 = 10 Mbps HD
Description
Read-only. Shows the fieldbus adapter type as
detected by the drive. The value cannot be
adjusted by the user.
If the value is 0 = None, the communication
between the drive and the module has not
been established.
Selects the application protocol and
communication profile for the network
connection.
The selections available for Modbus
communication are listed below.
Modbus/TCP: ABB Drives profile - Classic
Modbus/TCP: ABB Drives profile - Enhanced
Modbus/TCP: Transparent 16-bit profile
Modbus/TCP: Transparent 32-bit profile
Modbus over UDP: ABB Drives profile -
Enhanced
Modbus over UDP: Transparent 16-bit profile
Modbus over UDP: Transparent 32-bit profile
Sets the bit rate for the Ethernet interface.
Auto-negotiate
100 Mbps, full duplex
100 Mbps, half duplex
10 Mbps, full duplex
10 Mbps, half duplex
Modbus/TCP – Start-up
55
Default
128 =
ETHER-
NET
0 =
MB/TCP
ABB C
0 = Auto