FDNA-01 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
parameter group 51 in ACS355, ACSM1, ACS850 and
ACQ810
parameter group 51 in ACS880 if the adapter is installed as
fieldbus adapter A or group 54 if the adapter is installed as
fieldbus adapter B.
No.
Name/Value
01
FBA TYPE
02
MAC ID
ACS355:
FB PAR 2
ACSM1:
FBA PAR2
ACS850/ACQ810:
FBA par2
ACS880:
MAC ID
0...63
03
BAUD RATE
ACS355:
FB PAR 3
ACSM1:
FBA PAR3
ACS850/ACQ810:
FBA par3
ACS880:
Baud rate
0 = 125 kbit/s
1 = 250 kbit/s
2 = 500 kbit/s
Description
Read-only. Shows the fieldbus adapter type as
detected by the drive. Value cannot be adjusted
by the user.
If the value is 0 = None, the communication
between the drive and the module has not been
established.
Defines the MAC ID number for the drive the
adapter module is connected to. Each device
on the DeviceNet network must have a unique
MAC ID number.
MAC ID
Read-only. Indicates the detected
communication speed in kbit/s.
Communication speed is 125 kbit/s.
Communication speed is 250 kbit/s.
Communication speed is 500 kbit/s.
Start-up 35
Default
1 = Devi-
ceNet
63
0 = 125
kbit/s