24
Note: The new settings take effect only when the module is
powered up the next time or when the module receives a 'Fieldbus
Adapter parameter refresh' (Drive parameter 51.27) command
from the drive.

The REPL-01 configuration parameters

Par.
Parameter name Alternative settings
no.
1

MODULE TYPE

2
TRANSPARENT/
PROFILE MODE
3

NODE ID

1 MODULE TYPE
This parameter shows the module type as detected by the drive.
The value cannot be adjusted by the user.
If this parameter is undefined, the communication between the
drive and the module has not been established.

2 TRANSPARENT/PROFILE MODE

This parameter is used for choosing either the transparent (ABB
Drives) or the DSP 402 communication profile. This selection can
also be changed with object 0×2004 (hex).
3 NODE ID
Selects the node address of the module (1...239). Each device on
the Ethernet POWERLINK network must have a unique node
address (NODE ID). This parameter is used for defining a node
address for the drive it is connected to.
Note: If the node address is set via DIP switch S1, this parameter
is read-only. See chapter
Drive configuration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(Read-only)
(0) Profile mode (DSP 402)
(1) Transparent mode
(ABB Drives)
1 to 239
Electrical
Default setting
POWERLINK or Fieldbus
(0) Profile mode
(DSP 402)
1
installation.