60 Start-up
Parameter setting examples – ACS850 and ACQ810

ABB Drives profile

The following example shows how to configure the ACS850 or
ACQ810 drive to use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
The table below gives the recommended drive parameter settings.
Drive parameter
50.01 Fba enable
50.04 Fb ref1 modesel
50.05 Fb ref2 modesel
51.01 Fba type
51.02 FBA par2
(MAC ID)
51.03 FBA par3
(BAUD RATE)
51.06 FBA par6
(OUTPUT INSTANCE)
51.07 FBA par7
(OUTPUT NUM PARS)
51.08 FBA par8
(INPUT INSTANCE)
51.09 FBA par9
(INPUT NUM PARS)
52.01 FBA data in1
52.02 FBA data in2
Setting for
Description
ACS850/ACQ810
drives
1 = Enable
Enables communication between
drive and adapter module.
Speed
Selects speed as the adapter
module ref1 type.
Torque
Selects torque as the adapter
module ref2 type (only with
ACS850).
1)
DEVICENET
Displays the type of the adapter
module.
5
Defines the MAC ID number of the
adapter module.
0 (= 125 kbit/s)
Sets the baud rate for the
DeviceNet interface.
902
Selects the ABB Drives profile with
speed and torque plus drive
parameters output instance.
10
Must always be set to 10, except as
provided in
the number of drive
952
Selects the ABB Drives profile with
speed and torque plus drive
parameters input instance.
10
Must always be set to 10, except as
provided in
the number of drive
123
Motor power
0
Motor power - LSW
Appendix A – Varying
parameters.
Appendix A – Varying
parameters.