Starting up ACS880 drives

This example sets up the fieldbus adapter installed as fieldbus
adapter A. To set up the fieldbus adapter B, perform the same
tasks with the corresponding parameters in parameter groups 50,
54, 55, and 56.
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 FBA A enable to Enable.
3. Ensure that parameter 50.04 FBA A ref1 type is set to Speed
and parameter 50.05 FBA A ref2 type is set to Torque.
4. Set the FDNA-01 configuration parameters in drive parameter
group 51.
5. Define the process data transferred to and from the drive in
FDNA-01 parameter groups 52 and 53.
Note: If communication between the FDNA-01 and DeviceNet
master is established, changes to the configuration parameters
can be done also through
6. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter 51.27 FBA par refresh to Refresh.
7. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples – ACS880

ABB Drives profile

The following example shows how to configure the ACS880 drive
to use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
Fieldbus configuration object
Start-up 65