ODVA AC/DC drive profile

The following example shows how to configure the ACS850 or
ACQ810 drive to use the ODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
The table below gives the recommended drive parameter settings.
Drive parameter
50.01 Fba enable
50.04 Fb ref1 modesel
50.05 Fb ref2 modesel
51.01 FBA type
51.02 FBA par2
(MAC ID)
51.03 FBA par3
(BAUD RATE)
51.06 FBA par6
(OUTPUT INSTANCE)
51.08 FBA par8
(INPUT INSTANCE)
51.27 FBA par refresh
10.01 Ext1 start func
10.04 Ext2 Start func
Setting for
Description
ACS850/ACQ810
drives
1 = Enable
Enables communication between
drive and adapter module.
Speed
Selects speed as the adapter
module ref1 type.
Torque
Selects torque as the adapter
module ref2 type (only with
ACS850).
1)
DEVICENET
Displays the type of the adapter
module.
5
Defines the MAC ID number of the
adapter module.
0 (= 125 kbit/s)
Sets the baud rate for the
DeviceNet interface.
23
Selects the ODVA AC/DC drive
profile output instance.
73
Selects the ODVA AC/DC profile
input instance.
1 = Refresh
Validates the FDNA-01
configuration parameter settings.
3 = FB
Selects the fieldbus interface as the
source of the start and stop
commands for external control
location 1.
3 = FB
Selects the fieldbus as the source
for start and stop commands for
external control location EXT2 (only
with ACS850).
Start-up 63