FSCA-01 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
parameter group 51 in ACS355, ACSM1, ACS530, ACS850
and ACQ810
parameter group 51 in ACS880 if the adapter is installed as
fieldbus adapter A or group 54 if the adapter is installed as
fieldbus adapter B.
No.
Name/Value
01
FBA TYPE
02
Profile
0 = ABB Classic
1 = ABB Enhanced Modbus/RTU protocol with ABB Drives
2 = Transp 16
3 = Transp 32
03
Station ID
1...247
04
Baud rate
0 = 9.6 kbit/s
1 = 19.2 kbit/s
2 = 38.4 kbit/s
3 = 57.6 kbit/s
4 = 115.2 kbit/s
Description
Read-only. Shows the fieldbus adapter
type as detected by the drive. The value
cannot be adjusted by the user.
If the value is 0 = None, the communication
between the drive and the module has not
been established.
Selects the communication profile for the
network connection.
Note: The communication protocol is
selected with parameter
Modbus/RTU protocol with ABB Drives
profile - Classic
profile - Enhanced
Modbus/RTU protocol with Transparent 16-
bit profile
Modbus/RTU protocol with Transparent 32-
bit profile
Defines the address of the device. Two
units with the same address are not
allowed on-line.
Address of the device
Selects the baud rate of the link.
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
115.2 kbit/s
Start-up 35
Default
485 =
RS-485
0 = ABB
Classic
25
Protocol.
1
0 = 9.6 kbit/s