26 Modbus/TCP – Start-up
tables below and must be checked first and adjusted where necessary. You can adjust
the parameters via a drive control panel, a PC tool or a web user interface.
Note:
•
Not all drives display descriptive names for the configuration parameters.
•
The new parameter settings take effect only when you power up the module the
next time or when you activate the fieldbus adapter refresh parameter 51.27 FBA
A par refresh.
FMBT-21 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive type. Group A (group
1) corresponds to:
•
parameter group 51 in ACS380, ACS480, ACS580, ACH580 and ACQ580.
•
parameter group is typically 51/54 (group 151/154 in some variants) in ACS880 if
the adapter is installed as fieldbus adapter A/B.
No.
Name/Value
Description
01
FBA type
Read-only. Shows the fieldbus adapter type as detected by the
drive. The value cannot be adjusted by the user.
If the value is 0 = None, the communication between the drive and
the module has not been established.
02
Protocol/profile
Selects the application protocol and communication profile for
the network connection.
The selections available for Modbus communication are listed
below.
0 = MB/TCP ABB
Modbus/TCP: ABB Drives profile - Classic
C
1 = MB/TCP ABB
Modbus/TCP: ABB Drives profile - Enhanced
E
2 = MB/TCP T16
Modbus/TCP: Transparent 16-bit profile
3 = MB/TCP T32
Modbus/TCP: Transparent 32-bit profile
4 = MB/UDP
Modbus over UDP: ABB Drives profile - Classic
ABB C
5 = MB/UDP
Modbus over UDP: ABB Drives profile - Enhanced
ABB E
6 = MB/UDP T16
Modbus over UDP: Transparent 16-bit profile
7 = MB/UDP T32
Modbus over UDP: Transparent 32-bit profile
03
Commrate
Sets the bit rate for the Ethernet interface.
0 = Auto
Auto-negotiate
1 = 100 Mbps FD
100 Mbps, full duplex
2 = 100 Mbps
100 Mbps, half duplex
HD
3 = 10 Mbps FD
10 Mbps, full duplex
4 = 10 Mbps HD
10 Mbps, half duplex
Default
Mod-
bus/TCP
0 = MB/TCP
ABB C
0 = Auto