5. PARAMETERS
5. PARAMETERS
CAUTION
5.1 Parameter List
5.1.1
Parameter write inhibit
In the MR-J2-03A5 servo amplifier, its parameters are classified into the basic parameters (No. 0 to 19)
and expansion parameters (No. 20 to 49) according to their safety aspects and frequencies of use. In the
factory setting condition, the customer can change the basic parameter values but cannot change the
expansion parameter values. When fine adjustment, e.g. gain adjustment, is required, change the
parameter No. 19 setting to make the expansion parameters write-enabled.
Parameter No. 19 Setting
0000
(initial value)
000A
000B
000C
Never adjust or change the parameter values extremely as it will make operation
instable.
POINT
After setting the parameter No. 19 value, switch power off, then on to make
that setting valid.
Basic Parameters
Operation
No. 0 to No. 19
Reference
Write
Reference
Write
Reference
Write
Reference
Write
Expansion Parameters
No. 20 to No. 49
No. 19 only
No. 19 only
5 - 1