DC-Powered Systems

In sites where the Cisco 12012 operates with DC-input power supplies, observe the
following guidelines:
Each DC-input power supply requires a dedicated 60-amp service. Table 2-4 lists the
nominal and acceptable value ranges for source DC power.
For DC power cables, we recommend that you use 4-AWG, high strand count wire cable
(three leads).
Lugs should be dual hole and able to fit over M6 terminal studs at .625-inch (15.86-mm)
centers. Figure 2-3 shows the type of lug required for the DC-input cable connections.
Table 2-4
Specifications
DC input voltage
DC input current
1. VDC = volts direct current.
Figure 2-3
DC Power Cable Lug
End View
Ø .267
.55
2 holes
.25
.08
2-14 Cisco 12012 Gigabit Switch Router Installation and Configuration Guide
Source DC Power Specifications
Nominal Value
1
–48 VDC
(United States)
–60 VDC (International)
50 amps (@ 50 VDC)
2.25
Crimp area
.63
.37
Acceptable Value Ranges
–40.5 to –56 VDC (United States)
–58 to –75 VDC (International)
All measurements in inches
4 AWG conductor