Restoring Factory Settings - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Commissioning
56
To unlock the SIL mode and set the MIN fail-save mode:
1 →
7
3
-
+
5
A0042483
4 →
7
3
-
+
5
A0042494
The SIL mode is unlocked.
7.2.11

Restoring factory settings

This function allows you to restore the factory settings. This is particularly useful if
the device has already been calibrated once and, for example, there is a fundamental
change in the medium in the tank.
After restoring the factory settings, you must repeat the calibration.
Restoring factory settings
The device is set into the factory settings and it is possible to continue with setting the
measuring range and the calibration.
1 →
7
3
-
+
5
A0042452
2 →
1
7
7
3
-
+
5
A0042484
Set the function switch to
position 7.
5
7
1
7
3
-
+
5
A0042649
Set the function switch to
position 1.
2 →
7
3
-
+
5
A0042486
Press the  and  keys.
Liquicap M FTI51
3 →
7
3
-
+
5
> 4 s
A0042485
Press the  and  keys > 4 s.
3 →
7
3
-
+
5
> 20 s
A0042512
All LEDs light up sequentially
in time > 20 s.