Setting The Switch-Point Adjustment - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FTI51
Endress+Hauser
Carrying out full calibration
1 →
-
+
A0042514
4 →
2x
-
+
A0042521
The green LED 1 flashes
quickly to indicate that the
value has been saved correctly.
7.4.3

Setting the switch-point adjustment

If only one calibration (empty or full) was carried out, and if buildup forms on the rod
probe while the probe is in operation, the device may no longer respond to changes in
level. A switch-point adjustment compensates for this condition and ensures that you
obtain a constant switch-point again.
For media that do not have a tendency to build up, we recommend a setting of 2 pF,
as the probe is most sensitive to changes in level at this setting.
For media with heavy buildup, is recommended to use the probes with active buildup
compensation with the setting of 10 pF.
Switch-point adjustment:
 49
10 pF
 50
2 pF
2 →
-
+
A0042519
Make sure that the calibration
DIP switch is in position
"Covered".
5
1x
-
+
A0042522
The process of saving the full
calibration value is finished
when the green LED 1 flashes
slowly.
C
C
Commissioning
3 →
-
+
> 2 s
A0042520
Press the A and B keys > 2 s.
A0042406
A0042407
65