Setting The Alarm Response If The Measuring Range Is Exceeded; Setting The Measuring Range - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FTI51
Endress+Hauser
 41
FEI53 and FEI57S human interface
1
Green LED - operational status
2
Standard or alarm DIP switch
3
Measuring range DIP switch
4
Red LED - fault
7.3.1

Setting the alarm response if the measuring range is exceeded

The functions of the DIP switches:
 42
Standard: if the measuring range is exceeded no alarm is output
 43
Alarm: if the measuring range is exceeded an alarm is output
With this setting, is possible to determine the alarm response of the measuring
system when the measuring range is exceeded. It is possible to switch the alarm on or
off if the measuring range is exceeded.
All other settings concerning the alarm response have to be configured on the
respective Nivotester switching device.
7.3.2

Setting the measuring range

The functions of the DIP switches:
 44
Measuring range: the measuring range is between 0 to 500 pF. Span: the span is between 0 to 500 pF
1
2 3
4
0...1600pF
Standard
0.....500pF
FEI5x
-
+
1
2
Standard
0.....500pF
Commissioning
A0042395
A0042400
A0042401
A0042402
61