Setting The Switching Delay - Endress+Hauser Liquicap M FTI51 Operating Instructions Manual

Capacitance point level switch for liquids
Hide thumbs Also See for Liquicap M FTI51:
Table of Contents

Advertisement

Liquicap M FTI51
Endress+Hauser
7.2.8

Setting the switching delay

NOTICE
The tank can overflow if the switching delay is set for too long.
The switching delay causes the device to signal the point level after a delay. This is
highly useful in tanks with turbulent medium surfaces caused, for example, by the
filling process or by collapsing mounds. By doing so, you ensure that the filling of the
tank does not end until the probe is continuously covered by the medium.
A switching delay that is too short may, for example, cause the filling process to be
restarted as soon as the medium surface settles.
Setting the switching delay
1 →
1
5
7
3
-
+
5
A0042740
Set the function switch to
position 5.
4 →
_
= 5 s
7
3
-
+
5
A0042743
7 →
7
3
-
+
5
> 2 s
A0042746
Press the  key to decrease
the value.
2 →
_
= 1 5 s*
.
7
3
-
+
5
A0042741
The green LED 2 shows the
factory setting 1.5 s.
5 →
7
3
-
+
5
> 2 s
A0042744
Press the  to increase the
switching delay time.
8 →
_
= 5 s
7
3
-
+
5
A0043655
Commissioning
3 →
7
3
-
+
5
> 2 s
A0042742
Press the  to increase the
switching delay time.
6 →
_
= 10 s
7
3
-
+
5
A0042745
9 →
5
1
7
3
-
+
5
A0042747
Set the function switch to
position 1.
49